Technician's Checklist
Below is a checklist of items our technicians check each time they visit.
Items in blue and underlined indicate a hyperlink which will take you to an article with more information about this subject.
- Checked all filters – Filter qty. ____ Filter Size 1___________ Filter Size 2__________ Filter Size 3 _______ ( Type_________)
- Visual inspection of indoor registers, dirty, or, any complaints of hot or cold spots from home
- Central Air Purification, Is System Protected With UVC Technology? Yes/ Or if no Why _________Manuf. ________Model
- Visual, Return Air Grill, or door test for duct leaks – ducts sealed, insulation taped and in good shape
- Air handler electrical connections tight and clean_____________
- Blower motor sealed, or was lube performed ___________________________________
- Blower wheel clean and tight __________________________
- Any evidence of contaminants on evaporator or in air handler ____________________________
- Condensate Line flushed and draining ____________________________ q P Trap installed properly ____ Is it primed Y/N
- Condensate Algaecide pills added to drain pan _____________________ q Safety Switch in pan? _________________
- Any sounds of vibration or air leaking _________________________________________
- Thermostat: Digital or Manual? ______________________________________________ STICKER ON T-STAT.
- Is it level, secure, and batteries changed, this year? ______________________________
- Any sounds or symptoms before you touch customers unit? _________________________________
- Amperage draw of electric heat kit Name Plate ____ Actual ____ KW__________
- FLA on blower motor Name Plate ____ Actual ____
- FLA on inducer motor Name Plate ____ Actual ____
- Visual inspection of Burners______________ Heat Exchanger__________________ Combustion air motor ___________
- Carbon Monoxide Levels. ______________________________
- Gas pressures Nat – (Max – 10”WC Min-4.5”WC) Incoming ____ Outgoing(3.5”WC/1.5”WC) 1st Stg ____2nd Stg ____
Gas pressures LP – (Max – 14”WC Min-11.5”WC) Incoming ____ Outgoing(10.5”WC/7.5”WC) 1st Stg ____2nd Stg ____
With system stabilized and turned down low enough to not satisfy the thermostat, check the following:
- Delta T more than 2-3 degrees between rooms one room hotter or cooler________________________
- Supply temp ____ Return Temp ____ Difference ____
- Indoor Ambient ____ Indoor R/H ____ Indoor WET bulb ____ Humidification or Dehumidification needed? ________
- Checking charge in heat or cool? (Circle One)
- LLP ____ PTR ____ - LL Temp. ____ = Sub cooling ____ Required _____________ (HOT GAS TEMP____)
- Outdoor Dry Bulb ____ Indoor DB ________ Indoor WB ________
- SLP ____ SL Temp ____ -SL PTR ____ = Super heat ____ Required _____________
- Line voltage ________
- Blower motor CEMF ______
- Compressor CEMF ____
- Condenser fan motor CEMF ____
- LRA of compressor - Would a Hard start be helpful? Name Plate ____ Actual ____
- RLA of compressor Name Plate ____ Actual ____
- FLA of fan motor Name Plate ____ Actual ____
- Check contactor condition __________________________________________________
- All electrical connections tight and clean? _____________________________________
- Is a factory time delay in use? ________________
In Shut down Mode
- Blower motor Capacitor MFD Name Plate ____ Actual ____ %
- Condenser fan cap. Name Plate ____ Actual ____ % ____, & Compressor Cap. Name Plate_____ Actual_____ %______
- Megohmeter readings on compressor ______, condenser fan motor _____, and PSC type blower motor _____
- Is condenser free of leaves, dirt or debris? Course of action taken_____________________
- Accumulator rusty/leaking yes / no
- Circle one for each, does unit have txv on evaporator Yes / No, and On condenser Yes / No
- Condition of condenser coil ________________________
- Fan Blade condition ______________________________
- Any evidence of Leaks ____________________________
- Any rust ________________________________________
- Clean exterior of air handler ____________________________________
|
|
We provide rapid service to the following areas:
- Franklin County
- Grundy County
- Coffee County
- Lincoln County
- Moore County
- Bedford County
- Monteagle
- Sewannee
- McMinnville
- Bell Buckle
- Murfreesboro
- Eagleville
- Lewisburg
- Fayetteville
- Lynchburg
- Shelbyville
- Hillsboro
- Tullahoma
- Estill Springs
|